With a BENETECH GM505 differential pressure measurement, the sign belongs to the port arrangement. A negative value may mean the higher-pressure point is connected to the minus port, rather than that a filter has somehow produced an impossible result. Record which point is connected where before making a maintenance judgement.

The two pressure ports need a recorded upstream/downstream assignment; a sign alone is not a diagnosis.
Write the pressure relationship first
The GM505 has two metal pressure ports marked plus and minus and a listed differential range of ±2.49 kPa. For an ordinary signed differential measurement, the relationship is ΔP = P(+) − P(−), subject to the instrument's selected mode and instructions.
Suppose two suitable low-pressure test points are at 180 Pa and 60 Pa relative to a common reference. Connecting 180 Pa to plus and 60 Pa to minus produces an illustrative difference of +120 Pa, or +0.120 kPa. Reversing those connections gives −120 Pa. These are arithmetic examples, not a GM505 test or a filter acceptance threshold.

Assumed pressures share a common reference. The diagram does not establish a safe connection method, pressure compatibility or filter replacement threshold.
If the sign is unexpected, check the documented connection and operating conditions through a suitable procedure. Do not swap tubes casually on an unidentified or unsafe pressure system merely to obtain a positive number.
Check the whole pressure setup
A differential range describes the difference the instrument measures. It does not by itself specify the maximum safe pressure applied to each port, permissible common-mode pressure or compatibility with every medium. Two high absolute pressures could have a small difference and still be unsuitable for the instrument.
Confirm the medium, individual port pressures, tubing, fittings, connections and instrument limits before use. Do not infer refrigerant, fuel-gas, liquid or high-pressure compatibility from the generic word manometer. Use appropriate trained procedures for the actual system and keep test access within their scope.
With the correct safe arrangement, check the reference or zero procedure in the manual. A blocked tube, kink, leak or liquid in a pressure line can distort a comparison. Re-zeroing is not a substitute for repairing the setup or calibrating the instrument.
Compare a filter under comparable flow conditions
For a suitable filter-pressure application, identify upstream and downstream test points and keep that assignment fixed. Record the fan mode, relevant damper positions and other operating conditions. Pressure drop can change because airflow changes, not only because the filter condition changes.
A comparison made at a low fan setting before maintenance and a high setting afterwards cannot isolate the effect of the filter. The same caution applies if the filter type, housing, access panels or measurement points changed.
Use the system or filter manufacturer's specified limits and measurement method. There is no universal replacement threshold in the GM505's ±2.49 kPa range. A small reading is not automatically good ventilation, and a larger reading is not automatically proof of a blocked filter.
Keep units and display functions in the note
The instrument lists DIF, HOLD, UNITS and REC controls. Confirm exactly what the selected mode displays and how any stored or relative value is established. A held or referenced result may differ from the live port-to-port value you expected.
Keep Pa and kPa explicit: 1 kPa = 1,000 Pa. A decimal shift can create a much larger error than the apparent last-digit precision suggests. If results are exported or transcribed, carry the sign and unit together.
The listing includes an accuracy percentage without a sufficiently clear basis for a detailed uncertainty calculation here. Do not assume it means percent of reading or percent of full scale. Obtain the exact GM505 specification and calibration information if that distinction matters to the decision.
Hand over evidence rather than a verdict
Record the two connection points, port assignment, medium and permitted pressure conditions, zero procedure, mode, units, operating state and result. Note any unstable indication or tubing problem.
That makes a later comparison possible and separates three different issues: a changed process, a changed test arrangement and a potential instrument problem. The signed number becomes useful only when those conditions remain attached to it. For uncertainty and calibration concepts, see calibration and accuracy basics.