A current input only becomes an engineering value after the receiving system applies its scaling. The SG-002 lists analogue voltage output of ±12 V and current output from 0–24 mA, with battery and non-battery versions offered.

For a suitable 4–20mA input test, record both the injected current and the receiving channel's configured engineering range. A number on either device alone is only half the comparison.

SG-002 product view

SG-002 supplier product image. Screen values and accessory layouts are illustrative; confirm the selected version.

Confirm the connection mode first

Identify whether the receiving input expects an active current source or another connection arrangement. Check its isolation, permitted terminals, input limits and loop-power requirements against the SG-002 instructions. Current-source output and transmitter simulation are not interchangeable descriptions.

Do not connect an active source into an already powered loop on the assumption that all 4–20mA equipment can be combined. Establish the actual connection and power arrangement under a competent procedure. Isolate or disable consequential control actions before a test as the system procedure requires.

Check the selected SG-002 version and its power arrangement. The listed output spans do not independently establish every calibration mode, compliance-voltage capability or accuracy specification.

SG-002 rear terminal block and front selector views

Supplier connection-layout photograph; terminal mode must be verified before use.

Write the scaling before the test points

Suppose a receiving channel is intentionally configured so that 4 mA means 0% and 20 mA means 100%, with linear scaling. Under those assumptions, 12 mA represents 50%. These are illustrative scaling points, not measured SG-002 results or the correct settings for every process.

Write the actual engineering units beside the percentages. A pressure channel scaled from 0 to 10 bar and a temperature channel scaled from −20 to 80 °C would show different engineering values at the same current. Neither should be judged from an unlabelled “50”.

Keep a 4–20mA test tied to its scaling. 4 mA: 0% under the example linear scaling. 12 mA: 50% under that same assumption. 20 mA: 100% under that same assumption

Illustrative scaling only; verify source mode, loop power and input limits.

Keep the source and receiver records together

Use suitable test points under the approved procedure and allow the receiving system to settle. Record commanded current, independently verified current where required, displayed engineering value and any channel filtering or scaling settings relevant to the comparison.

If the result is wrong, separate a scaling problem from a wiring, source or input problem. A display at the wrong units may look like an electrical fault until the configuration is checked. Retain both the before and after settings when a correction is authorised.

Finish by restoring the system under its procedure and confirming that temporary test connections and control overrides have been removed. The SG-002 can provide a defined stimulus within its verified capabilities. A useful test record shows how that stimulus travelled through the configured input, rather than treating agreement at one point as complete calibration of the entire process.

For the current specification and supplied version, see the SG-002 product page.