1Panier

NOYAFA · Guide

NOYAFA NF-565 : consigner ensemble unités de pression et ordre des prises

Les unités de pression et l’ordre des prises de tuyaux du NOYAFA NF-565 doivent figurer dans le même relevé. L’appareil annonce 11 unités et une plage de ±35,1 kPa. Un changement d’affichage après UNIT ne doit pas êtr...

Par EkoDeluxe · Publié le · Mis à jour le

NOYAFA NF-565 product view

NOYAFA NF-565 pressure units and hose-port order belong in the same record. The store lists 11 selectable units and a ±35.1 kPa range. Check the supplied version and its resolution at the pressure drop you need to distinguish before ordering. A display change after pressing UNIT should not become an apparent change in the ventilation system.

Before a site visit, decide which unit the job requires and which location will connect to each port. Keep that convention through the inspection and any later report.

NOYAFA NF-565 product view

NOYAFA NF-565 supplier product photograph. Displayed values are illustrative.

Give the worksheet a unit before filling it

Use a column heading that includes the unit, such as “differential pressure, kPa”. Record the instrument's original displayed value as well as any converted result. This protects the context if someone later changes the worksheet's reporting unit.

For example, −0.05 kPa equals −0.5 mbar and −50 Pa. These are unit conversions, not NF-565 test results. A reading of 0.05 kPa is 50 Pa or 0.5 mbar. Converting the units preserves the pressure difference and its sign. Keep the original unit beside the conversion. A smaller reporting unit adds no measurement precision.

The listed choices include kPa, bar, mbar, psi and water-column units. Confirm the exact selected unit on the display. Be particularly careful with similarly named inch and centimetre water-column units, and use a documented conversion basis when moving between them.

The pressure is unchanged when its unit changes. −0.05 kPa: Original example value. −0.5 mbar: Same pressure difference. −50 Pa: Same pressure difference

Conversion example only • retain the port order and original value

Preserve the sign convention

In a simple differential arrangement, the reading represents P+ minus P−. Label each hose with its sampling location. If the positive port is at the lower pressure, a negative result can be expected; the minus sign is not automatically a fault code.

For a room comparison, write the relationship explicitly, such as “room at + port; corridor at − port”. Do not reverse hoses for a more convenient positive number without updating the record. That would change the meaning of the comparison.

Zero the instrument in the equal-pressure condition prescribed by its instructions. Do not zero away an unknown real system difference and then copy subsequent values as though the original reference remained intact. Note re-zeroing in the worksheet.

Add mode and observation window

The NF-565 lists HOLD, MAX, MIN, DIF and a TIME readout. Confirm how these modes operate and reset. A held value, an accumulated maximum and a live observation should have different labels in the record.

Define the observation window and record the fan setting, damper state and door positions. Pressure may change when one of those conditions changes. The timer display does not establish computer logging or an automatic sampling interval.

Check hoses for leaks, obstruction and trapped liquid, and verify pressure and medium compatibility before connection. A listed measuring span does not establish universal fluid compatibility or an overload limit.

Convert once, then review the comparison

For a final report, retain the original readings and apply the same documented conversion to the comparable values. Check that the sign, port relationship and event notes survive the transfer. Avoid typing converted numbers over the originals.

Pressure remains different from airflow: a pressure difference does not independently give CFM. Choose the NF-565 for the verified pressure task and use a record that makes its unit, reference and observation mode clear at every step.

For the current specification and supplied version, see the select the NOYAFA NF-565 differential manometer.