A higher air-speed reading after maintenance may be encouraging, but it does not automatically prove the maintenance caused the change. The BENETECH GT8907 digital anemometer can support a useful comparison when the fan state, probe position and surrounding conditions are kept consistent.
The aim is a paired observation: one clear baseline, one clearly described change and a repeated measurement at the same positions.

Define the change before collecting numbers
Write down exactly what is being compared. It might be an authorised filter replacement or a change in a permitted fan setting. Avoid combining several adjustments and then attributing the whole result to one of them.
Record the relevant operating conditions: fan setting, open or closed doors, damper state where applicable and the observation position. If a system controls its speed automatically, note that behaviour because it can complicate the comparison.
This is a practical investigation method, not a commissioning certificate or a substitute for the applicable ventilation test standard.
Reuse the same probe geometry
Mark or photograph the positions to be observed. Keep vane orientation, distance from the opening and the observation duration consistent. Avoid placing the user's body or the meter where it obstructs the flow.
A grille can have an uneven velocity profile. One central reading may not represent the whole opening. Use the appropriate spatial sampling method for the task, and retain the individual positions instead of recording only the largest value.

Keep temperature and speed in their own fields
The GT8907 listing includes wind-speed and air-temperature readouts. Preserve both quantities and their units if both are relevant. Temperature can help describe the operating state, but it is not a correction factor you can apply without a justified method.
The listing does not establish a complete airflow calculation function. Do not turn a speed reading into volume flow without the appropriate area and measurement assumptions. Airflow is useful conversational shorthand, but a report should say whether it contains velocity or volume flow.
Check the digital workflow before relying on it
USB and PC-software support are described for the BENETECH GT8907 listing. Confirm the actual supported software, connection and saving method before the comparison. A software feature from a similarly named Wintact WT8907 should not be carried over to this product.
If a file can be saved, open it and check the units and labels. If the available method is manual recording, use a prepared table and retain the original observations. Do not promise automatic logging or a particular sampling interval without verification.
Interpret a change with the conditions attached
Suppose the post-maintenance reading is higher but the fan setting also increased. The record supports a difference between the two states, not a clean estimate of the filter's effect. Repeat under matched conditions where appropriate, or state the limitation.
Likewise, a small difference close to the method's uncertainty may not support a strong conclusion. Anemometer accuracy needs to be considered alongside positioning and repeatability, which also affect a real comparison.
Keep the follow-up proportionate
A useful outcome can be a clearly observed change, no meaningful change, or an inconclusive comparison requiring a better method. Do not force every maintenance visit into a positive performance claim.
The GT8907 is most useful here as part of a documented before-and-after process, with the exact model, positions and operating states preserved alongside the numbers.

See the BENETECH GT8907 product page for the current version and kit, or read the BENETECH GT8907 overview before choosing.